Symptom
Unable to start the recording
function.
Unable to restart the
recording function.
*1 The following firmware versions are supported:
RnCPU or RnENCPU: '55' or later
RnSFCPU: '24' or later
*2 For the firmware versions, refer to the following:
Page 307 Added and Changed Functions
5 TROUBLESHOOTING
150
5.1 Recording Function
Check point
*1
Is a CPU module
or recorder module
version supporting a configuration with multiple modules
used, when using a camera recorder module with "Sub"
selected for the recording operation setting in the module
parameter?
(Page 95 Various operations settings)
Is a program changed by performing the online program
change or file batch online change?
Is a program changed by performing the online program
change or file batch online change while the battery voltage of
a CPU module is low?
Is the operating status of the recording function 'saving'?
Is a recorder module/camera recorder module
firmware version supporting SFC device sampling used when
setting SFC devices as sampling targets?
Corrective action
*2
with a firmware
• Update the module to a firmware version supporting the
configuration.
• Write the recording setting.
• Replace the battery with another one, then write the
recording setting.
• Wait for a recording file to be saved.
*2
with a
• Update the recorder module/camera recorder module to a
firmware version supporting it.