Error code
Error name
3002H
Module Parameter Error
3010H
Module Error
3013H
Module Error
3020H
Incompatible CPU Error
3021H
Recording Setting Error
3022H
Recording Setting Error
3023H to 3024H
Recording Setting Error
3025H
Recording Setting Error
3026H
Recording Setting Error
3027H
Recording Setting Error
3028H
Recording Setting Error
3029H
Recording Setting Error
3030H to 3031H
Recording Setting Error
5 TROUBLESHOOTING
172
5.6 Recorder Module
Error description
• A parameter which is not supported by the
firmware version of the target recorder
module was written.
• The contents in the module parameter are
broken.
The control CPU module does not support
the recording function.
A recording setting file which is not
supported by the firmware version of the
target CPU module was written.
• A recording setting file which is not
supported by the firmware version of the
target CPU module was written.
• The contents of the recording setting file
are broken.
• A recording setting file which is not
supported by the firmware version of the
target recorder module was written.
• The contents of the recording setting file
are broken.
The module type set in the engineering tool
does not match the CPU module which is
the write destination of the recording setting
file.
Device/label data which exceeds the size of
the buffer area for data sampling in the CPU
parameter is specified in the recording
setting file.
The program setting and FB/FUN file setting
in the CPU parameter in the CPU module
are different from the project (program
setting and FB/FUN file setting in the CPU
parameter) at recording setting.
• The program file and FB/FUN file in the
CPU module are different from the project
(program, FB/FUN) at recording setting.
• They are different from the program file
and FB/FUN file in the CPU module at
recording setting because the project
(program, FB/FUN) was changed during
recording operation.
The device/label operation is not set to
"Save" in the event history setting of the
CPU parameter.
A recording setting file which is not
supported by the firmware version of the
target recorder module was written.
Corrective action
• Please check the version of the recorder module, use
a compatible product, and then write the module
parameter again.
• Please write the module parameter again with the
engineering tool. If the same error is displayed again,
please consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the recorder module. Please
consult your local Mitsubishi representative.
Please use a CPU module which supports the
recording function.
Please check the version of the CPU module, use a
compatible product, and then write the recording file
again.
• Please check the version of the CPU module, use a
compatible product, and then write the recording file
again.
• Please take anti-noise measures.
• Please write the recording setting file again. If the
same error is displayed, a hardware error may have
occurred in the data memory of the CPU module.
Please consult your local Mitsubishi representative.
• Please check the version of the recorder module, use
a compatible product, and then write the recording
file again.
• Please take anti-noise measures.
• Please write the recording setting file again. If the
same error is displayed, a hardware error may have
occurred in the data memory of the CPU module.
Please consult your local Mitsubishi representative.
Please read the recording setting file, and match the
write destination CPU module and model type.
Please read the CPU parameter and recording setting
file, and reduce the device/label data to be saving
targets so that the size is within the buffer area for data
sampling in the CPU parameter. Or, please increase the
size of the buffer area for data sampling in the CPU
parameter.
• Please write the CPU parameter and recording
setting file to the CPU module.
• Please read the CPU parameter and recording
setting file, and write them to the CPU module again.
• Please write the program file, FB/FUN file, and
recording setting file to the CPU module.
• When the program file and FB/FUN file in the CPU
module were changed during recording operation,
please write the recording setting file to the CPU
module again.
• Please read the program file, FB/FUN file, and
recording setting file, and write them to the CPU
module again.
Please set device/label operation to "Save" in the event
history setting of the CPU parameter.
Please check the version of the recorder module, use a
compatible product, and then write the recording file
again.