5.8 Not Performing Measurements for Set Intervals

f
s-tmr
L
(S-TMR)
0
L
Displays "L 0."
amov
0
L
0
amov
0
L
00000
init
f
L
off
Displays "L f."
s-tmr
f
L
0. 0
s-tmr
f
L
00. 0
5-34
With this function measurement is not performed until a set time has
passed after the S-TMR input turns ON. (Timing starts at the rising
edge of the S-TMR input and the PV display is "-----" while no
measurement has been performed.)
If the power is turned ON while the s-tmr input is ON, measurement
will not start until the time set in the s-tmr elapses.
This can be used to create a waiting status until a rotating body
reaches its normal speed range when the power to the K3HB and the
rotating body is turned ON at the same time.
Use the following parameter to set the time.
Parameter
Startup compensation timer
s-tmr
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least 3 s in RUN level to move to
L
the initial setting level.
3 s min.
0" is displayed on the level/bank display to indicate the initial
• "
L
setting level.
B Press the M [MODE] Key several times to change the PV display
M
to "amov."
• This parameter is not displayed for the initial status due to setting
level protect.
Refer to "5.34 Limiting Key Operations" (P.5-84) for information on
removing setting level protect.
C Press the S [SHIFT] Key to make the SV display flash.
S
• The setting can be changed when the SV display starts to
flash.
D Use the U [UP] and S [SHIFT] Keys to set the password "-
U
0169." Press the M [MODE] Key to move to the advanced
function setting level.
M
f" is displayed on the level/bank display to indicate the
• "
L
advanced function setting level.
E Press the M [MODE] Key several times to change the PV display
M
to "s-tmr."
F Press the S [SHIFT] Key to make the SV display flash.
S
• The setting can be changed when the SV display starts to
flash.
Advanced function setting level
Set value
Meaning of set value
0. 0
Startup compensation timer disabled
0. . 1 to 99. 9
0.1 to 99.9 s