Section 5 Functions and Operations
5.12 Outputting for a Set Interval
f
shot
L
(SHOT)
5-44
The shot output function turns OFF a comparative output after a set
interval after it turns ON. The following diagram shows operation when
the shot output is set to 100 ms on the K3HB-R.
Comparative
set value H
Measurement value
Comparative
set value L
Output H
Output L
The shot output time is set using the following parameter.
Parameter
Shot output
shot
* The unit for K3HB-R settings is 100 ms. For example, if 10 is set,
then the shot output time is 10 × 100 ms = 1 s.
The shot output time is an internal calculation time. The following times
are added to the set time to give the actual output time.
• For relay outputs: 11 ms max.
• For transistor outputs: 1 ms max.
Advanced function setting level
100 ms
100 ms
Set value
Meaning of set value
0 to 1999
0 to 1,999 ms (0 to 199.9 s)*
The shot output will be
disabled when set to 0.
R
P C