Performing Output Tests - Omron K3HB-P User Manual

Digital indicators
Hide thumbs Also See for K3HB-P:
Table of Contents

Advertisement

Section 5 Functions and Operations

5.29 Performing Output Tests

t
test
L
(TEST)
0
L
Displays "L 0."
test
t
L
off
Displays "L t."
test
t
L
0
test
t
L
1234
123. 4
123. 4
5-74
The output test function is used to set test measurement values using
the keys to check the comparative outputs against the set comparative
set values.
A test measurement value is set using the following parameter.
Parameter
Test input
test
Note: With the K3HB-P, the setting range is 0 to 99999.
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least 3 s in RUN level to move to
L
the initial setting level.
3 s min.
0" is displayed on the level/bank display to indicate the initial
• "
L
setting level.
B Press the L [LEVEL] Key several times to move to the output
L
test level "test."
t" is displayed on the level/bank display to indicate the output
• "
L
test level.
C Press the S [SHIFT] Key.
S
• The test input will be 0 after moving to output test status.
D Use the U [UP] and S [SHIFT] Keys to change the set value.
U
• Use the U [UP] Key to increase the set value.
• Use the S [SHIFT] Key to decrease the set value.
• Continue pressing the key to quickly increase or decrease the
set value.
E Once the output test has finished, press the L [LEVEL] Key for
L
at least 1 s to return to RUN level.
1 s min.
Set value
Meaning of set value
off
Output test disabled
−19999 to 99999 (See note.)
- 1 9999 to
99999
Output test level
R
P C