5.19 Performing Linear Output

The linear output function outputs currents or voltages proportional to
measurement values as they change.
Select the type of linear output. Set the maximum and minimum output
measurement values to output the current or voltage for those
measurement values.
Voltage Output
Linear output
5 or 10 V
0 V
Linear output
Linear output
lower limit
upper limit
Current Output
Linear output
20 mA
0 mA
Linear output
Linear output
lower limit
upper limit
* If operation stops without performing a measurement, then the minimum
value (e.g., 4 mA for the 4 to 20 mA range) is output.
* The value set for the upper limit does not necessarily have to be higher than
the value set for the lower limit. The following is an example of reverse
scaling.
Linear output
20 mA
4 mA
Linear output
lower limit
* If the upper and lower limit are set to the same value, then the upper
limit will equals the lower limit plus 1 for linear output.
5.19 Performing Linear Output
Linear output
5 V
1 V
Measurement
Linear output
value
lower limit
Linear output
20 mA
4 mA
Measurement
Linear output
value
lower limit
Measurement
Linear output
value
upper limit
Linear output level
R
P C
Measurement
Linear output
value
upper limit
Measurement
Linear output
value
upper limit
5-57