Rotary Switches; Switch Factory Settings - YASKAWA SigmaLogic7 Compact Hardware Manual

Table of Contents

Advertisement

2 Specifications and Settings
2.1.2 400 V Specifications

2.3 Rotary Switches

When DIP switch 4 (E-INIT) is OFF, the rotary switches are ignored.
The IP address is set from configuration settings stored on the servo
controller.
Rotary switches are normally used to set the IP address. This is the
case when DIP switch 4 (E-INIT) is ON
 If both rotary switches are set to 0, use DHCP.
 If either rotary switch is non zero, the last octet of the IP address is set
by the value on the switches. Note that the switch values are labeled in
hexadecimal. The IP address will be 192.168.1.x where x is 0x01 to
0xFF for a decimal value of 01 to 255.
Rotary Switch 1

2.4 Switch Factory Settings

 All DIP switches off
 Rotary switches at 0 and 1.
 Configured IP address is 192.168.1.1
14
Rotary Switch 0
0
0
0
...
0
1
...
1
2
...
F
0
1
2
...
F
0
...
F
0
...
F
IP Address
Set by DHCP
192.168.1.1
192.168.1.2
...
192.168.1.15
192.168.1.16
...
192.168.1.31
192.168.1.32
...
192.168.1.255