Checking The Condensate Drain Pipe - Biasi BASICA COND User Manual And Installation Instructions

Table of Contents

Advertisement

sis check and adjustment if necessary as
described in the section "Gas valve - Ad-
justment - Chimney Sweep Mode" of the
Service manual.
Fig. 10.14
• Make sure that the ambient thermostat is
in the position "call for heat".
• Withdraw an abundant amount of D.H.W.
by opening the taps.
• Activate the "flue sweep function" at maxi-
mum heating power (see "Setting the
boiler flue sweep function" on page 80).
• Check the combustion of the boiler using
the outlets located on the flue tubes (Fig.
10.14) and compare the data measured
with that following.
Model BASICA COND 24C - M275V.2024 SM
Nominal heat input
(A) (E)
Nominal efficiency
Combustion efficiency
Air index
Flue gas CO
content
2
Flue gas O
content
2
Flue gas CO content
Flue gas temperature
Values refer to tests with a an 80 mm double exhaust
split by 1 + 1 m and natural gas G20 and a supply /
return heating temperature of 60°/80°C.
Fig. 10.15
MAINTENANCE
Flue analysis
points
kW
21,0
%
98,2
%
98,4
n
1,2
%
9,0 - 9,6
%
4,1
ppm
140
°C
82,0
Model BASICA COND 28C - M275V.2428 SM
Nominal heat input
(A) (E)
Nominal efficiency
Combustion efficiency
Air index
Flue gas CO
content
2
Flue gas O
content
2
Flue gas CO content
Flue gas temperature
Values refer to tests with a an 80 mm double exhaust
split by 1 + 1 m and natural gas G20 and a supply /
return heating temperature of 60°/80°C.
Fig. 10.16
Model BASICA COND 32C - M275V.2832 SM
Nominal heat input
(A) (E)
Nominal efficiency
Combustion efficiency
Air index
Flue gas CO
content
2
Flue gas O
content
2
Flue gas CO content
Flue gas temperature
Values refer to tests with a an 80 mm double exhaust
split by 1 + 1 m and natural gas G20 and a supply /
return heating temperature of 60°/80°C.
Fig. 10.17
The values in the tables are measured at
the nominal useful power with factory cali-
bration.
10.12 Checking the condensate
drain pipe
The condensate drain pipe 32 (Fig. 10.18)
does not require any particular mainte-
nance but just check:
• That no solid deposits have formed, if so
remove them.
• That the condensate drain piping is not
clogged.
kW
25,0
%
98
%
98,2
n
1,2
%
9,0 - 9,6
%
4,1
ppm
180
°C
85,0
kW
27,5
%
98,2
%
98,4
n
1,2
%
9,0 - 9,6
%
4,1
ppm
190
°C
83,0
- 79 -