Air Supply; Ventilation; Condensate Drain - Biasi BASICA COND User Manual And Installation Instructions

Table of Contents

Advertisement

5.5

Air supply

The room in which the boiler is installed does
not require a purpose provided air vent.
5.6

Ventilation

If installed in a cupboard or compartment, it is
not necessary to provide additional ventilation
for cooling for this particular product. However
consideration must be given to clearance re-
quirements for maintenance (section "Precau-
tions for installation" on page 44) and under
no circumstances must stored articles be al-
lowed to come into contact with the boiler or
flue pipe.
5.7

Condensate drain

Ensure that the condensate discharge com-
plies with the national or local regulations in
force.
The condensate pipe must be fitted in accord-
ance with Building Regulations.
Drain pipe material should be resistant to acid
as the condensate is slightly acid with a pH
less than 6.5.
The boiler includes a trap (32 on page 21)
that prevents the combustion products enter-
ing the drain.
The boilers incorporate a condensate trap with
a 225 mm seal to comply with BS 6798: 2008.
The schematic diagrams of possible connec-
tions are given in Fig. 5.2 and Fig. 5.3.
The length of the condensate pipe should be
kept to a minimum, any external pipe should
not be more than 3 m in 32 mm pipe and insu-
lated to prevent freezing.
To avoid condensate being trapped:
• the drain pipe should be run with a fall of at
least 2.5° (45 mm/m) away from the boiler;
• the number of bends and joints should be
kept at minimum;
• the drain pipe should be adequately fixed to
prevent pipe sagging.
- 40 -
- 40 -
GENERAL REQUIREMENTS
If a part of the drainpipe runs externally this
part should be kept as short as possible and
protected to reduce the risk of freezing.
Connection of condensate drainage pipe to
internal soil and vent stack.
Condensate
drain
C
Dimensions in mm
Fig. 5.2
A Boiler
B Internal soil and vent stack
C Invert
D 450 mm up to three storeys
Connection of condensate drainage pipe
downstream of a sink waste trap
Condensate
drain
E
Dimensions in mm
Fig. 5.3
A Boiler
E Sink
F Open end of condensate drainage pipe
direct into gully below grating but above
water level
Combined condensate and PRV discharge
It is possible to combine the PRV and conden-
sate discharge pipes providing the following
precautions are followed explicitly.
A
B
D
A
F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents