Manual Regeneration; Operation During A Power Failure - Pentair FOLEO 5800 XTR Installer Manual

Hide thumbs Also See for FOLEO 5800 XTR:
Table of Contents

Advertisement

7.4

Manual regeneration

From the home screen, press the regeneration button
Press now to begin a regeneration immediately, or press at regen. time to queue the regeneration
for the programmed regeneration time (2:00 AM default for softeners, 12:00 AM default for filters).
Pressing at regen. time again will cancel the manual regeneration.
1. During regeneration, press the button
in regeneration, the volume or time will be displayed below the button
Info
When a manual regeneration is launched, 100% of the resin bead is regenerated.
7.5

Operation during a power failure

The XTR controller includes internal power backup. In the event of power failure, the controller
shifts into a power-saving mode. The controller stops monitoring water usage. The display and
motor shut down, but it continues to keep track of the time and day for a minimum of eight hours.
The system configuration settings are stored in a non-volatile memory and are stored indefinitely
with or without power. After a long power outage, the time of day button may flash indicating it
needs to be reset. Press the button to stop the time of day from flashing and reset time if needed.
If power fails while the unit is in regeneration, the controller will save the current valve position
before it shuts down. When power is restored, the controller will resume the regeneration cycle
from the point where power failed. If power remains off for more than eight hours, upon power
restoration the regeneration is cancelled and the piston returns to service.
Caution - material
If power fails during a regeneration cycle, the valve will remain in its current position
until power is restored.
The valve system should include all required safety components to prevent overflows
resulting from a power failure during regeneration.
Ref. MKT-IM-038 / E - 22.10.2021
to access the regeneration screen.
Regeneration
now
at regen. time
to immediately advance to the next cycle step. Once
Installer manual Foleo 5800 XTR - Operation
.
67 / 108

Advertisement

Table of Contents
loading

Table of Contents