11.3.3 Output Specifications of the 64-point Digital Output Unit (Source Type)
■
Output specifications (source type)
Item
Insulation method
Output type
Rated load voltage
Allowable load voltage range
Max. load current
Common restrictions
Max. inrush current
OFF state leakage current
ON state max. voltage drop
Response time
External power
supply
Surge absorber
Short-circuit protection
Input points per common
Operating mode indicator
External connection method
■
Internal circuit diagram of the 64-point digital output unit (source type)
■
Limitations on the load current of the 64-point digital output unit (source type)
The load current is limited as shown in the following figure depending on the voltage of the
external power supply.
WUME-GM1H-02
Specifications
Optical coupler
Open collector
5 to 24V DC
4.75 to 26.4V DC
0.3A (20.4 to 26.4V DC), 30mA (4.75V DC)
3.2 A/common
0.6 A
1 µA or less
0.5 V or less
OFF→ON
0.1 ms or less (Load current: 2 mA or more)
ON→OFF
0.5 ms or less (Load current: 2 mA or more)
Voltage
4.75 to 26.4V DC
Current
90 mA/common (at 24 V)
Zener diode
None
32 points/1 common
32-point LED display (Lit when ON, selection using the display selector
switch)
Connector connection (Compliant with the MIL standard, 40P, two pieces
used)
11.3 Specifications of Expansion Units
11-11