5.3 Wiring of Input and Output
Two-wire output type
Precaution when using LED-equipped reed switch
When a LED is connected in series to an input contact such as LED-equipped reed switch,
make sure that the voltage applied to the GM1 input terminal is greater than the ON voltage. In
particular, take care when connecting a number of switches in series.
Precaution when using two-wire type sensor
If the input to the GM1 does not turn OFF because of leakage current from the two-wire type
photoelectric sensor or proximity sensor, connect a bleeder resistor as shown below.
Precaution when using LED-equipped limit switch
If the input to the GM1 does not turn OFF because of leakage current from the LED-equipped
limit switch, connect a bleeder resistor as shown on below.

5.3.3 High-speed Counter Input Wiring

● For the connection between the count input (phases A, B, Z) and encoder, etc., use
shielded twisted-pair cables.
● The length of connected wires should be 10 m or below.