7 Line Supply Connection
7.4 Line filters for I/R and UI modules
7.4.2

Wideband line filter

Description
Interfaces
Cooling clearance
Mounting
position
(wall mounting)
Cooling clearance
Note:
S
If the line supply and load connections are interchanged, this will immediately damage the components!
S
Carefully note the mounting position, base mounting is possible. Adequate heat dissipation must be ensured,
e.g. through the use of a fan.
Fig. 7-13
Wideband line filter (example 16 kW)
7-232
The damping characteristics of wideband line filters not only conform with the
requirements of EMC standards for the frequency range of 150 kHz to 30 MHz
but also include low frequencies as of 2 kHz. As a result, these line filters have
an extended function area, which means that they can, to a certain extent, be
used regardless of the machine installation location and any unknown line prop-
erties (e.g. line impedance).
The Wideband Line Filters should be preferably used.
TFor sinusoidal current operation, the total length of the power cables from the
line filter should not exceed 350 m and for square–wave current operation,
should not exceed 500 m!
U V W
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
Load connection (upper)
Warning and connection label
Rating plate
L1 L2 L3
Line supply connection (lower)
PE conductor (lower)
© Siemens AG 2012 All Rights Reserved