05.01
Analog setpoints
S
and actual values
S
Table 4-21
1)
The analog actual value inputs are differential inputs with an input resistance of
100 kΩ each.
The load capability of the 24 V outputs (P24RV1/2) is
S
S
for the mean current value with a load cycle of 10 s duration.
The temperature corner points may be interpolated linearly.
The short–term current rating of the 24 V outputs is 3.0 A (200 ms).
In the event of an overload, the F1900 or F1901 fuse on the ANA control unit
will blow.
Fuse
The switched 24 V outputs for axes 1 and 2 are protected by F1900 (axis 1) or
F1901 (axis 2) miniature fuses.
Value:
From:
Order No.:
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
X121:
Axis 1
X122:
Axis 2
Connectors X121, X122; both are 15pin sub–D socket connectors
Pin
X121
X122
1
P24RV1
P24RV2
2
P24RV1
P24RV2
3
P24RV1
P24RV2
4
P24RV1
P24RV2
5
M
M
6
USOLL1N
USOLL2N
7
USOLL1P
USOLL2P
8
M
M
9
M24EXT
M24EXT
10
M24EXT
M24EXT
11
M24EXT
M24EXT
12
13
M
M
14
UIST1N
UIST2N
15
UIST1P
UIST2P
I = Input, O = Output
for an ambient temperature of 40 °C
for an ambient temperature of 55 °C
2.5 AF/250 V; 5x20 mm UL
Wickmann–Werke GmbH
Annenstrasse 113
58453 Witten, Germany
or
Postfach 2520
58415 Witten
19194
4.4 "ANA module" control board
Type
Function
1)
O
P24EXT switched, from X431.5
O
P24EXT switched, from X431.5
O
P24EXT switched, from X431.5
O
P24EXT switched, from X431.5
Electronic ground
O
Analog setpoint output, reference ground
O
Analog setpoint output +/–10 V
Electronic ground
O
M24EXT , from X431.6
O
M24EXT , from X431.6
O
M24EXT , from X431.6
Not assigned
Electronic ground
I
Analog actual value input, reference ground
I
Analog valve actual–value input, +/–10 V
2.0 A
1.5 A
4 Control Units
4-117
4