Siemens 6SN1123-1AA00-0DA2 Configuration Manual page 100

Simodrive 611 series drive converter
Table of Contents

Advertisement

11.05
05.01
Table 4-10
Overview of the board–specific terminals and interfaces, continued
Terminal
Function
Function
No.
Designa-
tion
9
X431.3
Enable voltage
(+24 V)
663
X431.4
Pulse enable
(+24 V)
19
X431.5
Reference
(Reference for all digital
inputs)
Serial interface (X471)
X471
Serial interface for
"SimoCom U"
Equipment bus (X34)
X351
Equipment bus
Test sockets (X34)
DAC1
Test socket 1
DAC2
Test socket 2
X34
X34
M
Reference
1) I: Input; IO: Input/output; M: Measuring signal; NC: NC contact; S: Supply
2) Can be freely parameterized
3) When connecting contacts AS1/AS2 in series, a contact voltage drop up to max. 0.2 V must be taken into account for
the lifetime of the contacts (100000 switching operations). For a 24 V switching voltage, due to the non–linear contact
characteristics, from experience, five contacts can be simply connected in series without encountering any problems.
4) In accordance with EN 60204–1 (machine safety) control–power transformers should be provided when
AC control voltages are used.
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
4.2 "SIMODRIVE 611 universal HRS" control board
Type
Type
Technical specifications
Technical specifications
1)
1)
S
Reference:
Maximum current(for the total group):
Note:
The enable voltage (terminal 9) can be used to supply the
enable signals (e.g. pulse enable) as 24 V auxiliary voltage.
I
Voltage tolerance(including ripple):
Typ. current consumption:
Note:
The pulse enable acts simultaneously on drive A and drive B.
When this pulse enable is withdrawn, the drives "coast down"
unbraked.
S
Note:
If the enable signals are to be controlled from an external volt-
age source, the reference potential (ground) of the external
source must be connected to this terminal.
IO
Type: 9–pin D–sub socket connector
Cable diagram and pin assignment for RS232 or RS485, refer
to:
Reference:
/FB611U/ Description of Functions, SIMODRIVE 611 universal
IO
Ribbon cable:
Voltages:
Signals:
2)
M
Test socket:
Resolution:
Resolution:
2)
M
Rated operating voltage:
Rated operating voltage:
Maximum current:
M
4 Control Units
Terminal 19
Max. 500 mA
21 V to 30 V
50 mA at 24 V
34–pin
various
various
∅ 2 mm
8 bits
8 bits
0 V to 5 V
0 V to 5 V
Max. 3 mA
4-99
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents