Siemens 6SN1123-1AA00-0DA2 Configuration Manual page 196

Simodrive 611 series drive converter
Table of Contents

Advertisement

05.08
05.01
Table 6-24
Braking power of the UI and pulsed resistor modules (PR)
Description
External PR 0.3/25 kW
Order number
6SN1113–1AA00–0DA0
Can be used
28 kW UI module
for
for
Pn
0.3 kW
P
25 kW
max
E
7.5 kWs
max
Dimension drawings, refer to Chapter 12
1) External PR can also be used for damping after a protecting measurement on the HFD reactor.
Mounting
The resistor can be mounted either horizontally or vertically.
positions
Fig. 6-23
Fig. 6-24
Note
Conductors that are not used in multi–conductor cables must always be
connected to PE at both ends.
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
1)
External PR Plus 1.5/25 kW
6SL3100–1BE22–5AA0
28 kW UI module
PR module 6SN1113–1AB0V–0BAV
PR module 6SN1113–1AB0 –0BA
S
Attenuation: 0...230 kHz  3 dB
Attenuation: 0...230 kHz
S
Must be used together with HFD commutating reactor for damping
1.5 kW
25 kW
180 kWs
red, blue, PE (green yellow), each 1.5 mm
PE
Shielded 3 m connecting cable, can be extended up to max. 10 m
Connection for external pulsed resistor 0.3/25 kW
W/L3/D/L–
PE
U/L1/C/L+
V/L2
3R
1R
PE
The shield is connected through a PG gland
Shielded connecting cable (braided shield), cross–section 2.5 – 4 mm
max. length 10 m
Connection for external PR for braking power ratings up to 1.5/25 kW
6 Infeed Modules