Protection Control
Radiation fin temperature control
Perform the following control of integrated as well as multi units for each inverter compressor.
59
Normal operation
A
Reduce compressor capacity
Fin temperature standby
Condition
RXLQ72TATJU
A
more than 95°C (203°F)
B
less than 92°C (197.6°F)
C
more than 100°C (212°F)
Condition
RXLQ96/120TATJU
A
more than 70°C (158°F)
B
less than 67°C (152.6°F)
C
more than 75°C (167°F)
B
C
When occurring 4 times within 60
minutes, the error code L4 is output.
RXLQ72TAYDU
more than 96°C (204.8°F)
less than 93°C (199.4°F)
more than 100°C (212°F)
RXLQ96/120TAYDU
more than 70°C (158°F)
less than 67°C (152.6°F)
more than 75°C (167°F)
SiUS341802E
RXLQ72TAYCU
RXYQ72/96/120TAYCU
more than 90°C (194°F)
less than 87°C (188.6°F)
more than 95°C (203°F)
RXLQ96/120TAYCU
RXYQ144/168TAYCU
more than 90°C (194°F)
less than 87°C (188.6°F)
more than 95°C (203°F)
Functions and Control