Indoor Fan Motor Status Abnormality - Daikin Aurora Series Service Manual

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

Troubleshooting by Error Code
2.8

Indoor Fan Motor Status Abnormality

A6-20
Error Code
Applicable
FXTQ-TA
Models
Outline
The indoor unit periodically receives control status information from the fan motor.
Error is issued when the information shows abnormality.
Error Decision
If the information shows Power Limit or Temp Limit status, it will be deemed a MOTOR LIMIT
Conditions
abnormal operation. (The system can keep operating.)
If the information shows Motor Lost Control or Current Trip status, it will be deemed a MOTOR
TRIP abnormal operation. (The system stops operating.)
Error Reset
If the indoor unit stops receiving abnormal information, the error will be cleared.
Conditions
Supposed
Causes
Corrective
Actions
181
Fan or motor obstruction
Blocked filters
Power interruption (low voltage)
Incorrect wiring
Blockage in the airflow (ductwork) or ductwork undersized
High loading conditions
Check for obstruction on the fan, motor, or ductwork.
Clean filters.
Check filters, grille, duct system, heat exchanger air inlet/outlet for blockages.
Verify the input voltage at the motor.
Check wiring.
Replace motor.