Daikin Aurora Series Service Manual page 139

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

SiUS341802E
[2-27]: Night-time low noise operation stop time
3 (default)
This setting is used in conjunction with setting [2-22].
[2-28]: Power transistor check mode
To evaluate the output of the power transistors. Use this function in case error code is displayed related
to defective inverter PCB or inverter compressor is locked.
Default value: 0. Power transistor check mode is not active.
Field setting 1: Power transistor check mode is active.
Function:
Minimum requirements to refer to the result on the inverter checker module:
Cautions:
Field Settings and Test Operation
Value
Start time automatic night-time low noise
[2-27]
1
2
Inverter PCB gives output of 10 Hz in sequence by all 6 transistors. Remove the UVW terminals
of the inverter compressor, and connect to the inverter checker module. If all 6 LEDs blink, the
transistors switch correctly.
When the power transistor check mode is interrupted, after internal power circuit is disconnected
on the inverter PCB, 2 LEDs will light up to indicate discharge of the DC voltage. Wait till the LEDs
are OFF before returning fasten terminals back to the compressor terminals.
All 3 phases and neutral are available, and
Inverter PCB control is active. Check if the green LED "HAP" on the inverter PCBs are blinking
normal (approx. 1/ second). If LEDs are OFF, need to exit the "standby mode" of the inverter:
Disconnect and reconnect power supply control PCB, or
Forced thermostat ON condition, or
Make shortly set 2-6-1 (forced thermostat ON indoor), or 2-20-1 (manual refrigerant
charge).
Once the LED is blinking on the inverter PCB, change related setting immediately back to
set 0 to deactivate related function.
Diode module generates the required 500 VDC.
In case there is more than 1 compressor in a system (multi outdoor configuration), all compressor
inverter PCBs will perform the power transistor check. In such case, disconnect UVW fasten
terminals on all compressors. Avoid accidental touch of fasten terminals to short circuit or earth
leak to casing.
To stop the power transistor check mode, change setting to default 2-28-0.
Output to UVW will also stop when outdoor unit main PCB decides standby mode of inverter
circuit.
operation (approximately)
6:00 AM
7:00 AM
8:00 AM
Field Setting from Outdoor Unit
126

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents