Daikin Altherma 3 H HT F Series Installation Manual

Daikin Altherma 3 H HT F Series Installation Manual

Hide thumbs Also See for Altherma 3 H HT F Series:
Table of Contents

Advertisement

Installation manual
Daikin Altherma 3 H HT F
ETVH16S18DA6V(G)
ETVH16S23DA6V(G)
ETVH16S18DA9W(G)
ETVH16S23DA9W(G)
ETVX16S18DA6V(G)
ETVX16S23DA6V(G)
Installation manual
ETVX16S18DA9W(G)
English
Daikin Altherma 3 H HT F
ETVX16S23DA9W(G)

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Altherma 3 H HT F Series

  • Page 1 Installation manual Daikin Altherma 3 H HT F ETVH16S18DA6V(G) ETVH16S23DA6V(G) ETVH16S18DA9W(G) ETVH16S23DA9W(G) ETVX16S18DA6V(G) ETVX16S23DA6V(G) Installation manual ETVX16S18DA9W(G) English Daikin Altherma 3 H HT F ETVX16S23DA9W(G)
  • Page 2 3P586469-2A...
  • Page 3: Table Of Contents

    2-points curve ............. 22 Latest revisions of the supplied documentation may be available on 6.3.3 Slope-offset curve ............22 the regional Daikin website or via your dealer. 6.3.4 Using weather-dependent curves ....... 23 The original documentation is written in English. All other languages Settings menu ................
  • Page 4: About The Box

    ▪ The indoor unit is designed for indoor installation only and for the following ambient temperatures: ▪ Space heating operation: 5~30°C ▪ Space cooling operation: 5~35°C ▪ Domestic hot water production: 5~35°C Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 5: To Lower The Switch Box On The Indoor Unit

    "3.2.2 To lower the switch box on the indoor drain" [ 4  6] ▪ "3.3.2 To connect the drain hose to the ▪ When you need access to the high voltage switch box ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 6: To Close The Indoor Unit

    3 Slide the indoor unit into position. 3× 4 Adjust the height of the leveling feet to compensate for floor irregularities. The maximum allowed deviation is 1°. ≤1° Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 7: Piping Installation

    "7.2  Checklist 2 Cut out the rubber grommet on top of the unit, and remove the commissioning" [ 4  26]. during stop. The recirculation connector is placed below the hole. ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 8: To Fill The Water Circuit

    Ethylene glycol is toxic. piping from bursting, but NOT the liquid inside the piping from freezing. ▪ Protection against freezing: the glycol will prevent the liquid inside the piping from freezing. Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 9: To Fill The Domestic Hot Water Tank

    See the installation manual of the outdoor unit, or the installer ▪ [2.9] Control reference guide. ▪ [2.A] Thermostat type For the additional zone: Electrical installation ▪ [3.A] Thermostat type ▪ [3.9] (read-only) Control DANGER: RISK OF ELECTROCUTION ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 10: To Connect The Main Power Supply

    Maximum length: 200 m See below ("LAN adapter – System requirements"). LAN adapter – System requirements The requirements posed on the Daikin Altherma system depend on the LAN adapter application/system layout (app control, or Smart Grid application). Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 –...
  • Page 11: To Connect The Backup Heater Power Supply

    The backup heater capacity can vary, depending on the indoor unit model. Make sure that the power supply is in accordance with the backup heater capacity, as listed in the table below. ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 12: To Connect The Shut-Off Valve

    Maximum running current: 100 mA 230 V AC supplied by PCB [2.D] Shut off valve 1N~, 50 Hz 230 V AC unit" [ 4  4]): 1 Open the following (see "3.2.1 To open the indoor Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 13: To Connect The Electricity Meters

    X5M/6 and X5M/4; the negative polarity to X5M/5 and X5M/3. unit" [ 4  4]): 1 Open the following (see "3.2.1 To open the indoor 1 Top panel 2 User interface panel 3 Upper switch box cover ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 14: To Connect The Alarm Output

    A4P Installation of EKRP1HB is appropriate terminals as shown in the illustration below. required. Wires connected to the alarm output Wire between X2M and A4P A4P Installation of EKRP1HB is required. Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 15: To Connect The Changeover To External Heat Source

    2 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below. 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 16: To Connect The Safety Thermostat (Normally Closed Contact)

    After connecting the electrical wiring to the indoor unit To prevent water ingress to the switch box, seal the low voltage wiring intake using the sealing tape (delivered as accessory). Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 17: Configuration

    2 Go to [9.I]: Installer settings > Overview field settings. See also: settings" [ 4  17] ▪ "To access the installer settings" [ 4  25] ▪ "6.5 Menu structure: Overview installer ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 18: Configuration Wizard

    (User settings > Time/date) once the unit is initialised. 6.2.3 Configuration wizard: System Indoor unit type The indoor unit type is displayed, but cannot be adjusted. Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 19: Configuration Wizard: Backup Heater

    50°C, system is filled with glycol or water. This is important in case glycol is Daikin recommends NOT to disable the backup heater used to protect the water circuit against freezing. If NOT set second step because it will have a big impact on the correctly, the liquid in the piping can freeze.
  • Page 20: Configuration Wizard: Main Zone

    For more info about this functionality, see "6.2.5  Configuration zone" [ 4  20]. wizard: Main Code Description ▪ 0: Underfloor heating [3.7] [2‑0D] ▪ 1: Fancoil unit ▪ 2: Radiator Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 21: Configuration Wizard: Tank

    4  23]. The tank will heat up until the storage comfort temperature has been reached. It is the higher desired temperature when a storage comfort action is scheduled. ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 22: 2-Points Curve

    ▪ Change the slope to differently increase or decrease the temperature leaving water different ambient ▪ : Domestic hot water tank temperatures. For example, if leaving water temperature is in Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 23: Using Weather-Dependent Curves

    ON/OFF To fine-tune the weather-dependent curve: slope-offset curve condition. The following table describes how to fine-tune the weather- dependent curve of a zone or tank: ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 24: Additional Zone

    ▪ 2: 2 contacts 6.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 25: Menu Structure: Overview Installer Settings

    Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 26: Commissioning

    There are NO loose connections or damaged electrical commissioning checklist is also available on the Daikin components in the switch box. Business Portal (authentication required). There are NO damaged components or squeezed The general commissioning checklist is complementary to pipes on the inside of the indoor and outdoor units.
  • Page 27: To Perform An Operation Test Run

    ▪ Fill in the installer setting table (in the operation manual) with the Possible actuator test runs actual settings. ▪ Backup heater 1 test ▪ Backup heater 2 test ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 28 ▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 29: Technical Data

    Screw connection Pump Flare connection Backup heater Quick coupling Shut-off valve, male-female 1" Brazed connection Expansion vessel Magnetic filter/dirt separator Safety valve Air purge Drain valve Loose nut 1" ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 30: Wiring Diagram: Indoor Unit

    Only for preferential kWh rate Only for preferential kWh rate Legend power supply (outdoor) power supply (outdoor) Main PCB Outdoor unit Outdoor unit * On/OFF thermostat (PC=power circuit) Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 31 Only for wireless On/OFF Only for wireless On/OFF Safety thermostat contact: 16 V Safety thermostat contact: thermostat thermostat DC detection (voltage supplied 16 V DC detection (voltage by PCB) supplied by PCB) ETVH/X16S18+23DA6V+9W(G) Installation manual Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 32 & add: X2M: 3-4 Only for Human Comfort Interface 2 core 2×0.75 X5M: 11-12 A14P: P1-P2 user interface communication 2 core 2×0.75 A13P: P1-P2 LAN adapter communication 4D124705 Installation manual ETVH/X16S18+23DA6V+9W(G) Daikin Altherma 3 H HT F 4P586454-1 – 2019.07...
  • Page 36 4P586454-1 0000000U 4P586454-1 2019.07...