Field Setting from Outdoor Unit
[2-32]: Forced, all time, power consumption limitation operation (no external control adaptor is required to
perform power consumption limitation)
If the system always needs to be running under power consumption limitation conditions, this setting
activates and defines the level power consumption limitation that will be applied continuously. The level
is according to the table.
0 (default)
[2-34]: Indoor fan tap setting
Indoor fan speed limitation related to connection capacity and outdoor air temperature for energy saving.
0 (default)
∗ Indoor condition A: –1.5°C (–2.7°F) < Indoor air temperature – set temperature < 3°C (5.4°F)
∗ Indoor condition B: –1.5°C (–2.7°F) ≥ Indoor air temperature – set temperature, or ≥ 3°C (5.4°F)
129
Value
[2-32]
1
2
Value
[2-34]
Fan speed is limited to L tap when indoor units
capacity ≥ 130%.
In heating mode, fan speed is limited to L tap
1
when indoor units capacity ≥ 130%.
Fan speed follows a setting of the remote
2
controller (not limited by indoor units connection
capacity).
Fan speed is limited to L tap when outdoor air
temperature goes down to below 29.5°C (85.1°F)
and indoor condition A (∗). It returns to remote
3
controller setting when outdoor air temperature
goes up to over 32.5°C (90.5 °F) or indoor
condition B (∗).
Fan speed is limited to L tap when outdoor air
temperature goes down to below 23.5°C (74.3°F)
and indoor condition A (∗). It returns to remote
4
controller setting when outdoor air temperature
goes up to over 26.5°C (79.7°F) or indoor
condition B (∗).
Fan speed is limited to L tap when outdoor air
temperature goes down to below 19.3°C (66.7°F)
and indoor condition A (∗). It returns to remote
5
controller setting when outdoor air temperature
goes up to over 22.3°C (72.1°F) or indoor
condition B (∗).
Fan speed is limited to L tap when outdoor air
temperature goes down to below 29.5°C
6
(85.1°F). It returns to remote controller setting
when outdoor air temperature goes up to over
32.5°C (90.5°F).
Fan speed is limited to L tap when outdoor air
temperature goes down to below 23.5°C
7
(74.3°F). It returns to remote controller setting
when outdoor air temperature goes up to over
26.5°C (79.7°F).
Fan speed is limited to L tap when outdoor air
temperature goes down to below 19.3°C
8
(66.7°F). It returns to remote controller setting
when outdoor air temperature goes up to over
22.3°C (72.1°F).
Restriction reference
Function not active
Follows [2-30] setting
Follows [2-31] setting
Indoor fan tap setting
SiUS341802E