Operation of Downward Flow Flap (for FXEQ model)
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow
Model No.
13 (23)
Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Mode No.
13 (23)
∗Some indoor unit models are not equipped with draft prevention (upward) function.
Setting of the Static Pressure Selection (for FXDQ model)
Model No.
13 (23)
External Static Pressure Settings
FXMQ-PB model
Mode No.
13 (23)
The Second Code No. is set to 07 (an external static pressure of 100 Pa (0.40 inWG)) at factory setting.
∗1. FXMQ15/18/24/30/36/48PB cannot be set to 30 Pa (0.12 inWG).
∗2. FXMQ07/09/12PB cannot be set to 110-200 Pa (0.44-0.80 inWG).
∗3. FXMQ54PB cannot be set to 30 Pa (0.12 inWG) or 150-200 Pa (0.60-0.80 inWG).
Field Settings and Test Operation
First Code No.
Second Code No.
3
First Code No.
Second Code No.
4
First Code No.
Second Code No.
5
First Code No.
Second Code No.
6
01
02
01
02
03
Downward (Ceiling soiling prevention)
Standard (FXDQ07-12: 10 Pa (0.04 inWG),
01
FXDQ18/24: 30 Pa (0.12 inWG))
02
(FXDQ07-12: 15 Pa (0.06 inWG),
FXDQ18/24: 45 Pa (0.18 inWG))
01
02
03
04
05
06
07
08
09
10
11
12
150 Pa (0.60 inWG) (∗2) (∗3)
13
160 Pa (0.64 inWG) (∗2) (∗3)
14
180 Pa (0.72 inWG) (∗2) (∗3)
15
200 Pa (0.80 inWG) (∗2) (∗3)
Field Settings from Remote Controller
Contents
Equipped
Not equipped
Contents
Upward (Draft prevention)
Standard
Contents
High static pressure
Contents
30 Pa (0.12 inWG) (∗1) (∗3)
50 Pa (0.20 inWG)
60 Pa (0.24 inWG)
70 Pa (0.28 inWG)
80 Pa (0.32 inWG)
90 Pa (0.36 inWG)
100 Pa (0.40 inWG)
110 Pa (0.44 inWG) (∗2)
120 Pa (0.48 inWG) (∗2)
130 Pa (0.52 inWG) (∗2)
140 Pa (0.56 inWG) (∗2)