Daikin Aurora Series Service Manual page 137

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

SiUS341802E
[2-8]:
Te target temperature during cooling operation
0 (default)
[2-9]:
Tc target temperature during heating operation
0 (default)
[2-12]: Enable the night-time low noise function and/or power consumption limitation via external control
adaptor (DTA104A61/62)
If the system needs to be running under night-time low noise operation or under power consumption
limitation conditions when an external signal is sent to the unit, this setting should be changed. This
setting will only be effective when the optional external control adaptor (DTA104A61/62) is installed.
Default value: 0
To activate this function: 1
[2-13]: AIRNET address
When an AIRNET system will be used, outdoor unit needs an AIRNET address.
Also to facilitate the recognition of a system in the map lay out of the service checker type III, set each
system a unique address between 1 and 63.
When duplicating of AIRNET address, UC error code will appear on central control.
[2-16]: Heat pump lockout 1
Heat pump is always locked out when this setting is ON. If the indoor fan control needs to be changed or
the auto-backup function is required, refer to the setting [2-37].
0 (default)
[2-18]: Fan high static pressure setting
In order to increase the static pressure the outdoor fan is delivering, this setting should be activated. For
details about this setting, see technical specifications.
Default value: 0
To activate this function: 1
Field Settings and Test Operation
Value
[2-8]
2
3
4
5
6
7
Value
[2-9]
1
3
6
Value
[2-16]
1
Te target
Auto
6°C (42.8°F)
7°C (44.6°F)
8°C (46.4°F)
9°C (48.2°F)
10°C (50°F)
11°C (51.8°F)
Tc target
Auto
41°C (105.8°F)
43°C (109.4°F)
46°C (114.8°F)
Heat pump lockout 1
OFF
ON
Field Setting from Outdoor Unit
124