Humidification when Heating Thermostat is OFF
Setting to "Equipped" turns ON the humidifier if suction air temperature is 20°C (68°F) or above and turns OFF the
humidifier if suction air temperature is 18°C (64.4°F) or below when the heating thermostat is OFF.
Mode No.
15 (25)
Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries out residual
operation for one minute after the thermostat is stopped. (For the purpose of preventing dust on the air filter from
falling off.)
Mode No.
15 (25)
Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the unit, this setting is
unnecessary.
Mode No.
15 (25)
Individual Setting of Ventilation
This is set to perform individual operation of Energy recovery ventilator using the remote controller/central unit
when Energy recovery ventilator is built in.
(Switch only when Energy recovery ventilator is built in.)
Mode No.
15 (25)
Display of Contact Center (For BRC1E73 only)
You can turn OFF the display of "DAIKIN Contact Center" as "Contact for Service Display."
Mode No.
1b
Display of Error Codes on the Remote Controller (For BRC1E73 only)
Error code (four digits) is displayed for limited products.
Select two-digit display if four-digit display is not preferred.
Mode No.
1b
Field Settings and Test Operation
First Code No.
Second Code No.
1
First Code No.
Second Code No.
2
First Code No.
Second Code No.
3
First Code No.
Second Code No.
5
First Code No.
Second Code No.
3
First Code No.
Second Code No.
4
01
02
01
Without direct duct connection
02
01
02
01
02
01
02
01
02
03
04
Field Settings from Remote Controller
Contents
Not equipped
Equipped
Contents
With direct duct connection
Contents
Not interlocked
Interlocked
Contents
Not individual
Individual
Contents
Displayed
Not displayed
Contents
Two-digit display
Four-digit display
110