Daikin Aurora Series Service Manual page 152

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

Field Setting from Outdoor Unit
B. When the Normal demand operation is carried out. (Use of the external control adaptor for outdoor
unit is not required.)
1. While in setting mode 2, set the item 2-32 (Setting of alternate demand) to ON.
2. While in setting mode 2, select a demand 1 level for the item 2-30.
Image of operation in the case of A
Power consumption
Rated
70 %
40 %
Forced thermostat OFF
(Fan operation)
Image of operation in the case of B
Power consumption
Rated
70 %
139
If carrying out demand or low-noise input, connect the terminals
of the external control adaptor for outdoor unit as shown below.
To other external control adaptor
for outdoor unit
Demand level 1
Power consumption set by
Demand 1 level setting.
The power consumption set with Demand 1 level setting.
F1
F2
N
P
Demand
1
2
3 C
Host computer monitor panel or demand controller
Demand level 2
instructing
instructing
X1M
Low
noise
Outside
wiring
indicated by
dotted line.
Demand level 3
instructing
Field Settings and Test Operation
SiUS341802E
The power
consumption
during the
demand level 1
instructing can be
set with the
Demand 1 level
setting.
(70 % of rated
power
consumption has
been set at
factory.)
When the
Normal demand
setting is set to
ON (OFF has
been set at
factory.), the
power
consumption can
be set with the
Demand 1 level
setting. (70 % of
rated power
consumption has
been set at
factory.)