Daikin Aurora Series Service Manual page 148

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

Field Setting from Outdoor Unit
[2-97]: Auxiliary heater maximum allowable temperature
Auxiliary heater is allowed to energize when the outdoor air temperature is smaller than the auxiliary
heater maximum allowable temperature.
7 (default)
[2-98]: Auxiliary heater maximum allowable temperature release differential
Auxiliary heater is not allowed to energize when the outdoor air temperature is recovered by differential
above the auxiliary heater maximum allowable temperature.
1 (default)
135
Value
Auxiliary heater maximum allowable
[2-97]
0
1
2
3
4
5
6
8
9
10
11
12
13
14
Auxiliary heater always not allowed
15
Auxiliary heater always allowed
Value
Auxiliary heater maximum allowable
[2-98]
temperature release differential
0
2
temperature
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
12.7°C (55°F)
15.5°C (60°F)
18.3°C (65°F)
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
SiUS341802E
Field Settings and Test Operation