Field Settings from Remote Controller
Key-lock Pattern Settings (For BRC1E73 only)
Setting of key-lock pattern for the remote controller
Mode No.
1b
∗ When the Second code No. is set to 04, no menu operation is allowed without key-lock by pressing and holding
the menu button. Set the Second code No
Setting "Restricted / Permitted" of Airflow Block
(For units with the infrared presence/floor sensor only)
Due to possibility of dew condensation, the airflow block function cannot be enabled when closure material kit,
fresh air intake kit, natural / separately installed evaporation humidifier, or branch air duct is equipped.
This setting will prevent the airflow block is advertently set to ON.
Ensure that this setting is "Disable airflow block" when using together with options listed above.
Mode No.
1b
Room Temperature Display (For BRC1E73 only)
A "Detailed display screen" can be selected as the display screen. This setting is used if you do not want to
display "Room temperature display" on the "Detailed display screen."
Mode No.
1c
111
First Code No.
Second Code No.
12
.
First Code No.
Second Code No.
14
First Code No.
Second Code No.
0
01
02
(Cancel procedure is not displayed.)
03
04
No menu operation is allowed any time.
to other than 04 to cancel it.
01
02
03
04
05
01
02
Contents
No operation allowed
(Cancel procedure is displayed.)
No operation allowed
No menu operation is allowed.
Contents
Airflow block permitted
Airflow block restricted
Contents
Not displayed
Displayed
Field Settings and Test Operation
SiUS341802E