2.3
Operating the BS Buttons and DIP Switches on the Logic
Board
Operating the BS buttons
By operating the BS buttons it is possible to:
Perform special actions (testrun, etc).
Perform field settings (demand operation, low noise, etc).
Below procedure explains how to operate the BS buttons to reach the required mode in the menu, select the
correct setting and modify the value of the setting. This procedure can be used any time special settings and
regular field setting are discussed in this manual.
Setting definition: [A-B]
A: mode
B: setting
C: setting value
A, B and C are numerical values for field settings. Parameter C has to be defined. It can be a chosen from a set
(0, 1, 2, 3, 4, 5, ...) or regarded as an ON/OFF (1 or 0) depending on the contents. This is informed when the field
setting is explained.
INFORMATION During special operation (e.g., test run, etc.) or when an error happened,
Functions of the BS button switches which are located on the outdoor unit PCB (A1P)
Turn ON the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit(s) is established and normal, the segment
indication state will be as below (default situation when shipped from factory).
When turning ON the power supply: flashing as indicated. First checks on power supply are executed (1 ~ 2
minutes).
When no trouble occurs: lighted as indicated (8 ~ 10 minutes).
Ready for operation: blank display indication as indicated.
Segment display indications:
Off
Blinking
On
When above situation cannot be confirmed after 12 minutes, the error code can be checked on the indoor unit
user interface and the outdoor unit segment display. Solve the error code accordingly. The communication wiring
should be checked at first.
INFORMATION During special operation (e.g., test run, etc.) or when an error happened,
Field Settings and Test Operation
C
information will contain letters and numerical values.
information will contain letters and numerical values.
Field Setting from Outdoor Unit
118