Daikin Aurora Series Service Manual page 93

Hide thumbs Also See for Aurora Series:
Table of Contents

Advertisement

SiUS341802E
Note:
When the indoor unit is FXFQ, FXZQ or FXUQ, if the air outlet is set as dual-directional or tri-
directional, the starting conditions will be changed as follows.
Liquid pipe temperature ≤ 1°C (33.8°F) (for total of 15 minutes)
or
Liquid pipe temperature ≤ 0°C (32°F) (for 1 minute continuously)
Liquid pipe
temperature
(44.6˚F)
(32˚F)
OR
(44.6˚F)
(33.8˚F)
Functions and Control
During freeze-up prevention operation, the airflow rate is fixed to LL.
(The cancelling conditions are same as the standard.)
+7ºC
0ºC
1 min.
+7ºC
+1ºC
t1
t2
Freeze-up prevention control
Forced OFF by thermostat
Start
Freeze-up prevention control
Forced OFF by thermostat
t
>
15
t3
t4
Start
Outline of Control (Indoor Unit)
10 min.
Normal operation
Cancel
10 min.
Normal operation
minutes
Cancel
80