SiUS331708EA
2. Field Settings from Outdoor Unit
2.1
Capacity Setting
Caution
Be sure to carry out capacity setting after changing the main PCB (A1P) to spare PCB.
(for RXSQ48/60TAVJU only)
Attach the capacity setting adaptor corresponding to capacity class to connector X51A.
Capacity setting is not required for RXSQ24/36TAVJU.
X51A
Model
RXSQ48TAVJU
RXSQ60TAVJU
Field Settings and Test Operation
Adaptor type
J71
J56
Field Settings from Outdoor Unit
112