SiUS331708EA
3.1.2 Startup Control in Heating Operation
Electric symbol
Outdoor unit
actuator
24/36 class 48 class 60 class
Compressor
M1C
Outdoor fan
M1F
Four way valve
Y1S
Main electronic
Y1E
expansion valve
Subcooling
electronic
expansion valve
Hot gas bypass
Y2S
valve
Injection valve
Y3S
Ending conditions
Functions and Control
Thermostat ON
Pressure equalization control
prior to startup
M1C
M1C 0 Hz
From starting
M1F,
M1F
Ta > 20°C (68°F): STEP 1
M2F
Ta ≤ 20°C (68°F): OFF
Y1S
Y1S
Holds
Y1E
Y1E
0 pulse
Y3E
0 pulse
ON
Y3S
OFF
• Pc – Pe < 0.3 MPa
OR
(43.5 psi)
• A lapse of 5 min.
Startup control
STEP 1
Increases 2 steps every 20 seconds
from minimum frequency
Minimum frequency
until Pc – Pe > 0.39 MPa
(56.6 psi) is achieved
STEP 8
STEP 8
ON
ON
0 pulse
0 pulse
0 pulse
0 pulse
OFF
OFF
OFF
OFF
OR
A lapse of 10 sec.
Special Control
STEP 2
• A lapse of 130 sec.
• Pc > 2.70 MPa
(392 psi)
• Pc – Pe > 0.39 MPa
(56.6 psi)
46