Daikin RXSQ24TAVJU Service Manual page 137

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

SiUS331708EA
Setting of Demand Operation
By connecting the external contact input to the demand input of the external control adaptor for outdoor unit
(optional), the power consumption of unit operation can be saved suppressing the compressor operating
condition.
Set item
Demand
When the constant demand operation is carried out. (Use of the external control adaptor for outdoor unit
is not required.)
1. While in setting mode 2, set the item 2-32 (Constant demand) to ON.
2. While in setting mode 2, set the item 2-30 (Demand 1 level) and then set the setting condition to targeted
mode.
Image of operation
Power consumption
Rated
80%
70%
60%
Field Settings and Test Operation
Condition
Level 1
Level 2
Level 3
The power consumption set with Demand 1 level setting.
Content
The compressor operates at 60% or less of rating.
The compressor operates at 70% or less of rating.
The compressor operates at 80% or less of rating.
Field Settings from Outdoor Unit
When the
Constant demand
setting is set to ON
(OFF has been set at
factory.) , the power
consumption can be
set with the Demand 1
level setting. (70% of
rated power
consumption has been
set at factory.)
124