60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

Field Settings from Remote Controller
Auxiliary Electric Heater ON/OFF Temperature
Gas Furnace ON/OFF Temperature
Note: ∗1. S value varies automatically based on the room temperature trend.
FXFQ-T, FXMQ-PB
Mode No.
11 (21)
FXUQ-P, FXEQ-P, FXLQ-M, FXNQ-M, FXTQ-TA
Mode No.
11 (21)
There is a limitation of combination between Ton and Toff as below due to 2°C (3.6°F) hysteresis required for
reliability.
Second Code No.
06
05
04
03
02
01
: Available
— : Not available
CXTQ-TA
Mode No.
11 (21)
∗1. The second code No. 07 is used for disabling the starting of gas furnace interlocking with room temperature.
97
Thermostat
ON
First Code No.
Symbol
Ton
1
Toff
First Code No.
Symbol
1
Ton
2
Toff
01
–4°C
(–7.2°F)
0.5°C (0.9°F)
0°C (0°F)
–0.5°C (–0.9°F)
–1°C (–1.8°F)
–1.5°C (–2.7°F)
–2°C (–3.6°F)
First Code No.
Symbol
1
Ton
2
Toff
Set temperature
Thermostat
OFF
Toff + S(∗1)
Ton + S (∗1)
Second Code No.
01
02
03
–4°C
–3.5°C
–3°C
(–7.2°F)
(–6.3°F)
(–5.4°F)
–2°C
–1.5°C
–1°C
(–3.6°F)
(–2.7°F)
(–1.8°F)
Second Code No.
01
02
03
–4°C
–3.5°C
–3°C
(–7.2°F)
(–6.3°F)
(–5.4°F)
–2°C
–1.5°C
–1°C
(–3.6°F)
(–2.7°F)
(–1.8°F)
Ton
02
03
–3.5°C
–3°C
(–6.3°F)
(–5.4°F)
Second Code No.
01
02
03
–4°C
–3.5°C
–3°C
(–7.2°F)
(–6.3°F)
(–5.4°F)
–2°C
–1.5°C
–1°C
(–3.6°F)
(–2.7°F)
(–1.8°F)
SiUS331708EA
04
05
–2.5°C
–2°C
(–4.5°F)
(–3.6°F)
–0.5°C
0°C
(–0.9°F)
(0°F)
04
05
–2.5°C
–2°C
(–4.5°F)
(–3.6°F)
–0.5°C
0°C
(–0.9°F)
(0°F)
04
05
–2.5°C
–2°C
(–4.5°F)
(–3.6°F)
(–2.7°F)
04
05
06
–2.5°C
–2°C
–1.5°C
(–4.5°F)
(–3.6°F)
(–2.7°F)
–0.5°C
0°C
0.5°C
(–0.9°F)
(0°F)
(0.9°F)
Field Settings and Test Operation
06
–1.5°C
(–2.7°F)
0.5°C
(0.9°F)
06
–1.5°C
(–2.7°F)
0.5°C
(0.9°F)
06
–1.5°C
07 (∗1)
–100°C
(–148°F)
–98°C
(–144.4°F)