Power Supply Voltage Abnormality - Daikin RXSQ24TAVJU Service Manual

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

Troubleshooting by Error Code

4.13 Power Supply Voltage Abnormality

A8
Error Code
Applicable
FXSQ-TA, FXMQ-PB
Models
Method of Error
Error is detected by checking the input voltage of the fan motor.
Detection
Error Decision
When the input voltage of fan motor is 150 V or less, or 386 V or more.
Conditions
Supposed
Causes
Troubleshooting
177
Defective power supply voltage.
Defective connection on signal line.
Defective wiring.
Instantaneous power failure, others.
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the condition
of the power supply.
(1) Check if power supply
voltage is 208-230 V
± 10%.
(2) Check if there is power
open phase or
defective wiring.
(3) Check if power supply
voltage unbalance is
within 6 V.
There
are problems on
the condition of power
supply described
above.
NO
A8
Reoccurrence of
error.
NO
YES
YES
SiUS331708EA
Correct any fault.
Check and correct each wiring.
It is possible to have external
factor, such as brownout and
instantaneous power failure.
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxsq36tavjuRxsq48tavjuRxsq60tavju

Table of Contents