Discharge Pipe Temperature Abnormality - Daikin RXSQ24TAVJU Service Manual

60 hz
Hide thumbs Also See for RXSQ24TAVJU:
Table of Contents

Advertisement

Troubleshooting by Error Code

4.36 Discharge Pipe Temperature Abnormality

F3
Error Code
Applicable
All outdoor units
Models
Method of Error
Abnormality is detected according to the temperature detected by the discharge pipe thermistor.
Detection
Error Decision
The discharge pipe temperature rises to an abnormally high level.
Conditions
The discharge pipe temperature rises suddenly.
Supposed
Causes
Troubleshooting
CHECK 11
209
Defective discharge pipe thermistor (R2T)
Disconnection of discharge pipe thermistor (R2T)
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
When the
unit stops operating
because of an error, is the discharge
pipe temperature higher than
120˚C (248˚F)?
NO
Pull the discharge pipe thermistor out from
the outdoor unit PCB and then measure
the resistance with a multimeter.
Are the
discharge pipe thermistor
properties normal?
CHECK 11
YES
Refer to page 266.
YES
NO
SiUS331708EA
Short of refrigerant,
compressor failure, etc.
refrigerant system failure.
Replace the discharge
pipe thermistor (R2T).
Replace the outdoor
main PCB (A1P).
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxsq36tavjuRxsq48tavjuRxsq60tavju