SiUS331708EA
4.35 Electronic Expansion Valve Coil Abnormality
E9
Error Code
Applicable
All outdoor units
Models
Method of Error
Check continuity of electronic expansion valve coil.
Detection
Error Decision
No current is detected in the common (COM [+]) when power supply is ON.
Conditions
Supposed
Causes
Troubleshooting
CHECK 18
Service Diagnosis
Defective electronic expansion valve coil
Defective outdoor main PCB
Disconnection of connectors for electronic expansion valve
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn power supply OFF, and
turn power supply ON again.
Return to normal?
The connector of
outdoor main PCB (A1P)
for electronic expansion
valve is connected.
resistance of
electronic expansion
valve coil is normal.
CHECK 18
Refer to page 273.
YES
NO
NO
YES
The
NO
YES
Troubleshooting by Error Code
External factor other than error
(for example, noise etc.).
Ensure correct connection.
Replace the electronic
expansion valve coil.
Replace the outdoor main
PCB (A1P).
208