SiUS331708EA
1.3.2 Details of Field Settings for Indoor Unit
Filter Sign Setting
Setting
Model
FXDQ-M, FXTQ-TA, CXTQ-TA
Mode No.
10 (20)
Long Life Filter Type, Filter Cleaning Sign Time
When an Ultra long life filter is installed, the filter sign timer setting must be changed.
Mode No.
10 (20)
FXDQ-M, FXTQ-TA, CXTQ-TA
The filter cleaning sign display time can be changed.
Mode No.
10 (20)
Selection of Thermistor
Select a thermistor to control room temperature.
When the unit is not equipped with an infrared presence/floor sensor:
Mode No.
10 (20)
The factory setting for the Second Code No. is 01 and room temperature is controlled by the suction air
thermistor and remote controller thermistor.
When the Second Code No. is set to 02, room temperature is controlled by the suction air thermistor.
When the Second Code No. is set to 03, room temperature is controlled by the remote controller thermistor.
Field Settings and Test Operation
10(20)-1
Filter contamination heavy/light
10(20)-0
FXFQ-T
FXFQ-P
FXZQ-TA
FXZQ-M
FXUQ-P
FXEQ-P
FXSQ-TA
FXMQ-PB
FXHQ-M
FXLQ-M
FXNQ-M
FXAQ-P
First Code No.
0
First Code No.
1
First Code No.
1
First Code No.
2
01: Long life filter
Light
01
2,500 hrs.
200 hrs.
Second Code No.
01
02
Second Code No.
01
02
Second Code No.
01
02
Second Code No.
Remote controller thermistor and suction air
01
thermistor for indoor unit
02
Suction air thermistor for indoor unit
03
Remote controller thermistor
Field Settings from Remote Controller
02: Ultra long life filter
Heavy
Light
02
01
1,250 hrs.
10,000 hrs.
100 hrs.
200 hrs.
Contents
Light
Heavy
Contents
Long Life Filter
Ultra Long Life Filter
Contents (Light/Heavy)
2,500/1,250 hours
10,000/5,000 hours
Contents
Heavy
02
5,000 hrs.
100 hrs.
94