6
|
Technical data

6.8 Field settings

6.8.1 Field settings: Outdoor unit

To access mode 1 or 2
To use mode 1
Service manual
170
1 Check if the unit is in normal mode. If NOT in normal mode, push BS1 to
return to normal mode. 7‑segment display indication state will be as shown:
Result:
2 7‑segment display indications:
Off
Blinking
On
3 BS1 is used to change the mode you want to access.
Access
Mode 1
Mode 2
Mode 1 is used to monitor the status of the unit.
What
Changing and accessing the
setting in mode 1
To quit and return to the initial
status
Example:
Checking the content of parameter [1‑20] (to know the outdoor unit air sensor
temperature).
[A‑B]=C in this case defined as: A=1; B=20; C=the value we want to know/monitor:
1 Make sure the 7‑segment display indication is as during normal operation
(default situation when shipped from factory). 7‑segment display indications:
Off
Blinking
On
2 Push BS1 one time.
Result: Mode 1 is accessed:
3 Push BS2 20 times.
Result: Mode 1 setting 20 is addressed:
Push BS1 one time.
7‑segment display indication changes to:
Push BS1 for at least 5 seconds.
7‑segment display indication changes to:
Once mode 1 is selected (push BS1 one time),
you can select the wanted setting. It is done by
pushing BS2.
Accessing the selected setting's value is done by
pushing BS3 one time.
Press BS1.
Action
How