Installer Manual Riversoft - Programming
5.8.
Calendar override setting
The controller needs a method to set days between regeneration for regulatory requirements and in
cases when the flow sensor has failed.
A
Press and hold
→ The programmed calendar override is displayed.
B
Press
to increases value.
→ Range from 0 through 30;
0 = Disabled;
0.3 = Regeneration every 8 hours : at 2, 10 and 18 hours;
0.5 = Regeneration every 12 hours : at 2 and 14 hours;
1 - 30 = Regeneration every X days (every 3 days in this
example).
5.9.
System selection
The controller has four system settings available. The system selections accommodate multiple tank
sizes and various feedwater conditions.
System selection:
A
Press and hold
→ A small "u" will be displayed in the left digit.
→ The right digit will display the current system setting.
B
Press
until desired system setting appears then release.
→ The displayed system setting will be stored in flash memory
when the controller exits programming after 5 seconds.
5.10. Regeneration cycles time
C#
Cycle
C1
Backwash
Brine draw
C2
Slow rinse
C3
Repressurize
C4
Rapid rinse
C5
2nd backwash
C6
2nd rapid rinse
C7
Brine refill
48 / 90
and
for 3 seconds.
and
simultaneously for 3 seconds.
Resin bed
flow
direction
↑
Calculated
↓
None
↓
↑
↓
None
Calculated
System u# [minutes]
u1
u2
8
8
Calculated
25
45
3
3
3
3
1
1
1
1
Calculated
Ref. MKT-IM-045 / A - 13.03.2020
u3
u4
1
3
Calculated
Calculated
25
45
3
3
1
3
1
1
1
1
Calculated
Calculated