Installer Manual Riversoft - Installation
the power outlet must be grounded;
to disconnect power, unplug the AC cable from its power source;
do not use any extension cord;
locate cord where it cannot be accidentally unplugged or cause any bodily harm.

4.3.4. Mechanical

CAUTION
Do not over-tighten the pipe to piping boss.
CAUTION
Do not put excessive force on the inlet, outlet or drain connections of the valve.
Do not use petroleum-based lubricants such as vaseline, oils, or hydrocarbon-based lubricants.
Use only 100% silicone lubricants;
all plastic connections should be hand tightened. PTFE (plumber's tape) may be used on
connections that do not use an o-ring seal. Do not use pliers or pipe wrenches;
all plumbing must be completed according to local codes;
soldering near the drain line should be done before connecting the drain line to the valve.
Excessive heat will cause interior damage to the valve;
observe the drain line requirements:
maximum 1 m high at 2 bars inlet pressure. Add 50 cm for additional 1 bar at the softener's inlet;
do not use lead-based solder for sweat solder connections;
the valve is designed for minor plumbing misalignments. Do not support the weight of the
system on the valve fittings, plumbing, or the bypass;
it is not recommended to use sealants on the threads. Use PTFE (plumber's tape) on the threads
of the 25.4 mm (1") NPT elbow, the drain line connections, and other NPT/BSP threads.