Checking And Maintenance (Generator; Generator - Kubota WSM J Series Workshop Manual

Diesel generator
Table of Contents

Advertisement

J SERIES, WSM

[8] CHECKING AND MAINTENANCE (GENERATOR)

(1) Generator

(A) Check Points of Every 300 Hours
(B) Check Points of Every 1000 Hours
(C) Check Points of Every 1 year
Brush Wear
1. Check to see if the brush has worn to more than 1/2 below the
standard dimensions.
2. If wear exceeds the allowable limit, replace.
Standard length
Brush length (Stretch
out of the Holder)
Allowable limit
H : Brush Length
Slip-ring
1. Check to see if there is no unusual wear and surface roughness.
Factory spec.
Slip-ring O.D.
Correction limit
(1) Slip-ring
Checking Ball Bearing
1. Measure radial dislocation of the outer ring.
2. If the axial dislocation exceeds the allowable limit, replace the
bearing.
Axial dislocation
Allowable limit
1. Measure the I.D. of the bearing housing.
2. If the wear exceeds the allowable limit, replace the end bracket.
I.D. of bearing housing
Allowable limit
(1) Ball Bearing
Checking Damage in Electric Wiring and Loose Connections
Refer to "SERVICING" section.
S-37
GENERAL
15.0 mm
0.59 in.
7.5 mm
0.30 in.
W12095240
64.0 mm
2.50 in.
62.5 mm
2.50 in.
W12098350
0.05 mm
0.002 in.
90.02 mm
3.54 in.
W12101460
W1362595
KiSC issued 10, 2016 A

Hide quick links:

Advertisement

Table of Contents
loading