Kubota WSM J Series Workshop Manual page 52

Diesel generator
Table of Contents

Advertisement

J SERIES, WSM
(C) Voltage Faults (Three Phase)
Trouble
Checking Method
Voltmeter
Measure the voltage
indicates
at the output terminal
normal
using a circuit tester.
voltage but
no output
At AC range
voltage is
250 V or 500 V
delivered.
Terminals between
O and U,
O and V,
O and W.
Voltmeter
Same as above.
does not
Set the circuit
indicate
breaker to ON.
any voltage
and also
no output
voltage is
delivered.
Measurement
Operating
Possible Cause
Condition
Output voltage
Circuit breaker (NFB) is
is 0 V for all
OFF.
three phases.
Defective contact of
circuit breaker.
0 V for one
Defective contact of
phase only.
circuit breaker.
Two other
Discontinuity in one
phases are
phase.
normal.
0 V output
Discontinuity in output
for all three
coil.
phase.
Simultaneous shorting of
three phases.
0 V for one
Discontinuity in one
phase only.
phase.
Discontinuity in wiring.
Slight voltage
Discontinuity in rotor coil.
output for all
three phases.
Wear or defective
2 to 4 V (phase
contact of brush.
voltage).
Discontinuity in sub-coil.
A.V.R. failure.
Disconnected battery.
S-6
GENERAL
Countermeasure
Set the circuit breaker to
ON. If it goes OFF again,
check the cause
(overload, short circuit,
etc.).
Set the circuit breaker to
ON after removing the
cause.
Replace
Replace
Repair or replace the
stator.
Repair or replace the
stator.
Inspect the stator or
wiring.
Repair or replace the
stator.
Repair
Repair or replace the
rotor.
Clean brush contact
surface and slip ring
surface, or replace the
brush.
Repair or replace the
stator.
Replace
Connect battery
W1198623