Mechanical Connection Of The Cabinet Units; Connecting The Cooling Circuit Collecting Pipes - Siemens SINAMICS S120 Manual

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Mechanical installation
3.3 Installing
3.3.5

Mechanical connection of the cabinet units

3.3.5.1

Connecting the cooling circuit collecting pipes

Description
The collecting pipes of the cooling circuit must be connected during the installation of the
cabinet units or transport units. The collecting pipes are located at the rear lower cabinet
area.
The pipe couplings to connect the collecting pipes are included when shipped in the
accessory kits of the cabinet unit. The pipe couplings are called "PLAST-GRIP".
Figure 3-12
58
PLAST GRIP pipe coupling
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A

Advertisement

Table of Contents
loading

Table of Contents