Siemens SINAMICS S120 Manual page 224

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules
6.4 Heat Exchanger Modules
Table 6- 38
Technical data of the Heat Exchanger Modules, line voltage 3 AC 500 ... 690 V
Article No.
Deionized water circuit in the converter
Cooling power
Intake temperature
- min.
- max:
- <IP55 (drive line-up)
- IP55 (drive line-up)
Intake pressure
- min
- max
Rated flow rate
2)
Volume of liquid
Connection, intake/return
- outer diameter x wall thickness
Plant-side raw water circuit
Intake temperature
- min.
- max:
- <IP55
- IP55
Intake pressure, max.
Rated flow rate
2)
Pressure drop at the rated flow rate
Connection, intake/return
- outer diameter x wall thickness
General data
Supply voltages
- Line voltage
- Line frequency
- Electronics power supply
Current consumption
- Total operating current 690 V 3 AC, 50/60 Hz
- Electronics current (24 V DC)
Power consumption, max., 3 AC 690 V,
50/60 Hz
Power loss, max., dissipated to the ambient air
4)
Sound pressure level L
pA
Material of the integrated heat exchanger
Degree of protection (standard version)
222
6SL3705-
kW
°C
°C
°C
bar
bar
l/min
dm³
mm
°C
°C
°C
bar
l/min
kPa
mm
V
Hz
V
A
A
kW
kW
(1 m) at 50/60 Hz
dB(A)
0RG23-
2AA5
7)
32
1)
45
40
1.7
6.0
88
20.4
76.1 x 2.0
5
3)
38
33
6.0
132
50
42.0 x 1.5
3 AC 500 -10 % ... 3 AC 690 +10 %
ACrms
DC
4.4/4.1
1.0
3.5/4.7
0.5
<65
Stainless
steel
IP55
0RG24-
0RG27-
8AA5
2AA5
7)
7)
48
72
1)
1)
45
45
40
40
1.7
1.7
6.0
6.0
132
197
21.4
30.5
76.1 x 2.0
76.1 x 2.0
5
5
3)
3)
38
38
33
33
6.0
6.0
198
263
60
70
42.0 x 1.5
76.1 x 2.0
50 Hz
24 (20.4 ... 28.8)
4.4/4.1
6.4/7.0
1.0
1.0
3.5/4.7
5.5/6.4
0.5
0.5
<65
<65
Stainless
Stainless
steel
steel
IP55
IP55
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
0RG31-
1AA5
7)
120
1)
45
40
1.7
6.0
267
32.5
76.1 x 2.0
5
3)
38
33
6.0
445
90
76.1 x 2.0
6.4/7.0
1.0
5.5/6.4
0.5
<65
Stainless
steel
IP55

Advertisement

Table of Contents
loading

Table of Contents