Diagnostics
8.4 LEDs on the CBE20 Communication Board
Table 8- 8
Meaning of the Sync and Fault LEDs on the CBE20
LED
Color
Fault
Red
Sync
Green
Table 8- 9
Meaning of the OPT LED on the Control Unit
LED
Color
OPT
Green
Red
Orange
314
State
Description
Off
If the link port LED is green:
The CBE20 is operating error-free, and data is being exchanged with the configured
IO controller.
Flashing
- The watchdog timer has elapsed.
light
- Communication has been interrupted.
- The IP address is incorrect.
- Incorrect or missing configuration.
- Incorrect parameter assignment.
- Incorrect or missing device name.
- IO controller not present/switched off but Ethernet connection present.
- Other CBE20 errors.
Steady
CBE20 bus error
light
- No physical connection to a subnet/switch.
- Incorrect transmission rate.
- Full-duplex transmission is not activated.
Off
If the link port LED is green:
Control Unit task system is not synchronized with the IRT clock. An internal substitute
clock is generated.
Flashing
Control unit task system has synchronized with the IRT clock and data is being ex-
light
changed.
Steady
Task system and MC-PLL have synchronized with the IRT clock.
light
State
Description, cause
OFF
Electronics power supply is missing or outside permissible tolerance range.
The CBE20 is defective or not inserted.
Steady
CBE20 is ready and cyclic communication is taking place.
light
Flashing
CBE20 is ready but cyclic communication is not running.
light
Possible causes:
0.5 Hz
- Communication is being established.
-At least one fault is present.
Steady
Cyclic communication via PROFINET has not yet been established. However, acyclic
light
communication is possible. SINAMICS is waiting for a parameterization/configuration
telegram.
Flashing
The firmware download to the CBE20 has failed.
light
Possible causes:
0.5 Hz
- The memory card of the Control Unit is faulty.
- The CBE20 is out of order.
The CBE20 cannot be used in this state.
Flashing
Communication between the Control Unit and the CBE20 is faulty.
light 2 Hz
Possible causes:
- The CBE20 was removed following power-up.
- The CBE20 is defective.
Flashing
Firmware is being updated.
light
0.5 Hz
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A