9.41 M70, EMC shield bus

9.41
M70, EMC shield bus
9.41.1

General information

Availability of option
This option is available for the following S120 Cabinet Modules:
● Basic Line Connection Modules
● Active Line Connection Modules
● Motor Modules
● Heat Exchanger Modules
● Auxiliary Power Supply Modules
Description
With option M70, an EMC shield bus is incorporated for the use of shielded power cables for
power cables and motor supply cables.
The cable shields for the cables routed to the cabinet must be connected to the EMC shield
bus in accordance with EMC guidelines. The shields can be applied over a large surface
area with the supplied EMC shield clips.
9.41.2

Connecting the cables to the EMC shield bus

Preparatory steps
● Allow unimpeded access to the EMC shield bus (if necessary, remove the protective
covers during installation work)
Securing the cables to the shield bus
1. Remove approximately 5 cm of the protective sheath of the cable around the shield bus.
2. Place the shielded cable on the shield bus.
3. Snap the clip into the opening provided and tighten it.
446