Diagnostics
8.3 LEDs on the CU320-2 PN Control Unit
Behavior of the LEDs after booting
Table 8- 6
Control Unit CU320-2 PN – Description of the LEDs after booting
LED
Color
RDY
–
(READY)
Green
Red
Red/
green
Orange
Green/
orange
or
red/
orange
COM
–
PROFIdrive
cyclic opera-
tion
Green
Red
312
State
Description, cause
Off
The electronics power supply is missing or out-
side the permissible tolerance range.
Steady light
The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
Flashing light
Commissioning/reset
0.5 Hz
Flashing light
Writing to the memory card
2 Hz
Flashing light
PROFIenergy energy saving mode is active
0.5 s on, 3 s
off
Flashing light
General errors
2 Hz
Flashing light
Control Unit is ready for operation.
0.5 Hz
However, there are no software licenses.
Flashing light
Updating the firmware of the connected DRIVE-
0.5 Hz
CLiQ components
Flashing light
DRIVE-CLiQ component firmware update has
2 Hz
been completed. Wait for POWER ON of the
respective component.
Flashing light
Component recognition via LED is activated.
2 Hz
Remark:
Both options depend on the LED status when
activating p0124[0] = 1.
Off
Cyclic communication has not (yet) taken place.
Remark:
PROFIdrive is ready for communication when the
Control Unit is ready (see LED RDY).
Steady light
Cyclic communication is taking place.
Flashing light
Full cyclic communication has not yet taken
0.5 Hz
place.
Possible causes:
The controller is not transferring any set-
•
points.
During isochronous operation, no global con-
•
trol (GC) or a faulty global control (GC) is
transferred by the controller.
"Shared Device" is selected and only one
•
controller connected.
Flashing light
Bus error,
0.5 Hz
incorrect parameter assignment/configuration
Remedy
Check power supply
–
–
–
–
Check parameterization /
configuration data
Upgrade licenses
–
Carry out POWER ON for
the components in question
–
–
–
–
Adapt configuration be-
tween controller and devic-
es