P. WIRING - COMMUNICATING SYSTEMS:
Use extra CAN connectors provided with communicating furnaces and/or SMART HUB accessories and field provided wiring.
After installation, the installer must verify that the refrigerant leak detection system actuates all mitigating actions listed above.
The test can be initiated by shorting the two test pins on the header of the mitigation control board inside of the unit. The mitigating
actions will continue for approximately 5 minutes. See Figure 20 above.
If any of the mitigating actions are not actuated by the system during the test, please check the
following:
All field wiring connections should be checked against the diagrams in the "Field Wiring
Diagrams," page 15 section of this manual.
The diagnostic indicators on the mitigation control board should be checked against the
diagnostic codes given in below.
Scan the QR code below for more information on field troubleshooting of the refrigerant leak
detection system.
Q. AHC BOARD CONNECTIONS:
R: TROUBLESHOOTING THE REFRIGERANT
DETECTION SYSTEM:
If MCB is showing active alarm at startup:
Check harness connections at MCB and sensor. Wait 20
seconds to see if mitigation clears.
If refrigerant is detected, the 5 minute timer can be reset by
cycling power to the unit.
T. FLASH CODES:

FLASH CODES

MCB COMM (AMBER LED)
OFF
No Power/Off or in 24V mode
ON
24V mode active
NODE COUNT
Communication Mode Active/Normal Operation SLOW BLINK
FAST BLINK
CAN Communication lost
NOTE: All Past Alarm flash codes are present for 30 days post occurrence.
18-AD47D1-1B-EN
Installer's Guide
S. CONTROL BOX RELOCATION (OPTIONAL):
The control box may be relocated from the coil cabinet to allow
for clearance to braze connections, condensate connections,
or other space constraints, with use of extension kit optional
accessory BAYMCBHARNESS. To avoid puncturing
refrigerant tubes, it is not recommended to screw control box
to coil cabinet.
FLASH CODES MCB STATUS (GREEN LED)
OFF
No Power/Off
ON
Start Up
Normal Operation
Active Alarm - Refrigerant Leak,
3
Sensor Comm Error or Sensor Error
4
Past Refrigerant Detected Alarm
5
Past Sensor Comm Error
6
Past Sensor Error
13