Chapter 8 Optional Cards

8-3 EMC-D42A

I/O Extension
Card
MO10~MO11
8-4 EMC-D611A
I/O Extension
Card
8-5 EMC-R6AA
Relay Extension
Card
C2000 Series
Terminals
Common for Multi-function input terminals
COM
Select SINK NPN /SOURCE PNP in J1 jumper / external power
supply
Refer to parameters 02-26~02-29 to program the multi-function
inputs MI10~MI13.
Internal power is applied from terminal E24: +24Vdc±5% 200mA,
5W
MI10~ MI13
External power +24VDC: max. voltage 30VDC, min. voltage
19VDC, 30W
ON: the activation current is 6.5mA
OFF: leakage current tolerance is 10 A
Multi-function output terminals (photocoupler)
The AC motor drive releases various monitor signals, such as drive
in operation, frequency attained and overload indication, via
transistor (open collector).
Common for multi-function output terminals MO10,
MO11(photocoupler)
MXM
Max 48VDC 50mA
Terminals
AC power Common for multi-function input terminal (Neutral)
AC
Refer to Pr. 02.26~ Pr. 02.31 for multi-function input selection
Input voltage: 100~130VAC
Input frequency: 47~63Hz
MI10~ MI15
Input impedance: 27Kohm
Terminal response time:
ON: 10ms
OFF: 20ms
Terminals
Refer to Pr. 02.36~ Pr. 02.41 for multi-function input selection
Resistive load:
5A(N.O.) 250VAC
5A(N.O.) 30VDC
R10A~R15A
Inductive load (COS 0.4)
R10C~R15C
2.0A(N.O.) 250VAC
2.0A(N.O.) 30VDC
It is used to output each monitor signal, such as drive is in
operation, frequency attained or overload indication.
Descriptions
MO10
MO11
MXM
Descriptions
Descriptions
8-10