The Input/Output Mapping Areas - Delta DVP-ES3 Series Operation Manual

Hide thumbs Also See for DVP-ES3 Series:
Table of Contents

Advertisement

You can read emergencies from a slave through a PLC ladder diagram.
6.
It supports the SYNC object (synchronous object) service.
7.
Several devices can operate synchronously through the synchronous object service.
8.
The supported CANopen communication rates are: 20K, 50K, 125K, 250K, 500K, and 1Mbps.
The supported mapping data types are:
Storage
8-bit
SINT USINT BYTE
16-bit
INT UINT WORD
32-bit
DINT UDINT REAL DWORD
64-bit
LINT ULINT LREAL LWORD
The CAN port has the following functions when acting as a slave.
It supports the standard CANopen protocol DS301 V4.02.
It supports the NMT (network management object) service.
It supports the NMT state control.
The state of the DVP-ES3 Series in the CANopen network is controlled by a master.
It supports the NMT error control.
The DVP-ES3 Series supports Heartbeat but not Node Guarding.
It supports the PDO (process data object) service.
The PDO message transmits the immediate input data and output data.
It supports up to 8 TxPDO and 8 RxPDO.
The PDO transmission type: synchronous mode and asynchronous mode
It supports the emergency service.
If an error or an alarm occurs in the DVP-ES3 series, the master is notified through the emergency
service.

10.1.2 The Input/Output Mapping Areas

The following table lists the CANopen DS301 specifications for the AS DVP-ES3 Series PLC.
Type
Item
Maximum slave nodes
Master
Maximum transfer size of
a PDO (Read + Write)
Maximum transfer size of
Slave
a PDO (Read + Write)
C h a p t e r 1 0 C A N o p e n F u n c t i o n a n d O p e r a t i o n
Data type
Description
Up to 64 nodes
Up to 2000 Bytes (including some system configurations)
Up to 8 PDOs; each PDO with up to 8 bytes can be transferred
at a time
10
1 0 - 3